Kyoritsu · KEW 1051
Kyoritsu KEW 1051 True RMS Digital Multimeter
High-accuracy True RMS multimeter (0.09% basic DC V) rated CAT IV 600 V / CAT III 1000 V, with a low-pass…
Checking motor supply, running current, rotation and winding insulation.
Motors fail from insulation breakdown, single-phasing, overload and wrong rotation. Many failures can be predicted from simple measurements.
Phase sequence before first start, running current per phase, supply voltage balance, and insulation resistance of windings (including PI/DAR trends for larger machines).
A phase indicator, a clamp meter for running current, a multimeter with a low-pass filter for drive-fed motors, and an insulation tester suited to the motor voltage.
Listed because their documented specifications cover this measurement. Check the full specifications for your exact requirement.
Kyoritsu · KEW 1051
High-accuracy True RMS multimeter (0.09% basic DC V) rated CAT IV 600 V / CAT III 1000 V, with a low-pass…
Low-pass filter for measurements on motor-drive (inverter) outputs.
Kyoritsu · KEW 3125B
5 kV high-voltage insulation tester: 250 V to 5000 V, readings to 1 TΩ, PI/DAR diagnostics, noise filter and…
PI and DAR insulation diagnosis at up to 5 kV.
Kyoritsu · KEW 8031
Rugged phase indicator for 110–600 V three-phase supplies: checks phase sequence and open phase in one unit…
Phase sequence check before connecting three-phase motors.
Kyoritsu · KEW 2117R
True RMS AC clamp meter to 1000 A with 0.01 A resolution, 33 mm jaw and CAT IV 300 V / CAT III 600 V rating.
Measures AC running current up to 1000 A True RMS.
Kyoritsu · KEW 3552
Fast (0.5 s) insulation/continuity tester with six test voltages from 50 to 1000 V, readings to 40 GΩ…
PI and DAR diagnostic tests on insulation.
For low-voltage motors a 500 V or 1000 V insulation tester is common; larger or medium-voltage machines need higher test voltages and PI/DAR functions. Follow the motor manufacturer's test recommendations.
Isolate and lock off the motor before insulation testing, discharge windings after the test, and never insulation-test through a drive without disconnecting it.